logo

Testing Machine

Testing Machine

Testing Machine

RIGID STEEL CONDUITS

AS PER IS:9537(PART-II) 1981 SPECIFICATION

Nominal Size in mm 20 25 32 40 50
Outside Diameter-OD(mm) 20 25 32 40 50
Tolerance on OD (mm) -0.30 -0.40 -0.40 -0.40 -0.50
Minimum OD(mm) 19.70 24.60 31.60 39.60 49.50
Wall Thickness          
(a)    Minimum (mm) 1.40 1.40 1.40 1.60 1.60
(b)   Maximum (mm) 1.80 1.80 1.80 2.20 2.20